C - 39
(Continued)
Appendix C: Parameter Summary Numeric Quick Reference (continued)
Minimum Value: 0
Maximum Value: 999999
Default Value: 0
Units: Ratio
CP-230 Direct SP
Direct Setpoint (CP-230) is active only in Direct Mode (CP202=0). It sends a voltage value directly to the Control
Output (CO_Sig) terminal. Run/Stop commands are recognized, but no other control function is active. All encoder
signals are ignored.
Minimum Value: -15.0
Maximum Value: 15
Default Value: 0.0
Units: Volts
CP-231 Acl Tm Drct
Acceleration Time Direct (CP-231) is the time, in seconds, that it takes to accelerate from 0 to the CO Max Volts (CP-271)
voltage, while operating in the Direct Mode.
Minimum Value: 0
Maximum Value: 3600
Default Value: 3.000
Units: Seconds
CP-232 Dcl Tm Drct
Deceleration Time Direct (CP-232) is the time, in seconds, that it takes to decelerate from the CO Max Volts (CP-271)
voltage to 0 volts, while operating in the Direct Mode.
Minimum Value: 0
Maximum Value: 3600
Default Value: 3.000
Units: Seconds
CP-240 Jog SP
Jog Setpoint (CP-240) is the speed, in EU/Tm, at which Jog ramps when it is activated. The Jog ramp rates are
referenced to this speed.
Minimum Value: 0
Maximum Value: 999999
Default Value: 200
Units: EU/Tm
CP-241 Acl Tm Jog
Acceleration Time Jog (CP-241) is the time, in seconds, to accelerate from 0 to the Jog SP (CP-240).
Minimum Value: 0.0
Maximum Value: 3600
Default Value: 1.000
Units: Seconds
CP-242 Acl Rt Jog
Acceleration Rate Jog (CP-242) is the rate, in EU/Tm per second, that it takes to accelerate when Jog is activated.