Cp-380 cmpr1 parm, Cp-381 cmpr2 parm, Cp-382 cmpr3 parm – CONTREX CX-1200 User Manual
Page 403
![background image](/manuals/334431/403/background.png)
C - 57
(Continued)
Appendix C: Parameter Summary Numeric Quick Reference (continued)
CP-380 Cmpr1 Parm
Enter a Monitor Parameter code in Compare 1 Parameter (CP-380) that will act on the value in Cmpr1 Val (CP-388), by
using the comparison type that you entered in Cmp1 Type (CP-384). If the comparison that is established by these three
parameters is “true”, then the PLC sets the Cmpr1 Out bit (60) in the PLC to “1”, which can be used to trigger a user
defined indicator.
Minimum Value: 1
Maximum Value: 199
Default Value: 32 (VelError)
Units: Parameter Code
NOTE: The following Monitor Parameters are not available for the Cmpr1 Parm (CP-380), Cmpr2 Parm (CP-381), Cmpr3
Parm (CP-382) or Cmpr4 Parm (CP-383):
MP-12 LdJobSpcVar
MP-13 LdJbSzAvg
MP-22 FbJobSpcVar
MP-23 FbJbSzAvg
MP-41 ScaleFactor
MP-42 ActScaleFactor
MP-49 Cntrl Loop
MP-52 InvalidBlks
MP-53 Misc Status
MP-54 Std Alarms
MP-55 Custom Alms
MP-56 Misc Alarms
MP-90 SerCom Char In
MP-91 SerCom Errs
MP-94 ROM Test
MP-95 SRAM Test
MP-96 NV RAM Test
MP-97 MODEL #
MP-98 RELEASE
MP-99 REVISION
MP-100 DI 7..0
MP-101 DI 15..8
MP-102 DO 7..0
MP-103 KeyPad Lockout
MP-108 PLC Mon 1 Val
MP-109 PLC Mon 2 Val
MP-110 PLC 15-8
MP-111 PLC 23-16
MP-112 PLC 31-24
MP-113 PLC 39-32
MP-114 PLC 47-40
MP-115 PLC 55-48
MP-116 PLC 63-56
MP-117 PLC 71-64
MP-118 PLC 79-72
MP-119 PLC 87-80
MP-120 PLC 95-88
MP-121 PLC 107-100
MP-122 PLC 115-108
MP-123 PLC 123-116
MP-124 PLC 131-124
MP-125 PLC 139-132
MP-126 PLC 147-140
MP-127 PLC 155-148
MP-128 PLC 163-156
MP-129 PLC 171-164
MP-130 PLC 179-172
MP-131 PLC 187-180
MP-132 PLC 195-188
MP-133 PLC 203-196
MP-134 PLC 211-204
MP-135 PLC 219-212
MP-150 Last Reset
MP-151 Misc Intrpt
MP-152 Device Alms
MP-153 PC at Intrpt
MP-156 Mem Err Cntr
MP-157 WatchDogCntr
MP-158 MiscIntrptCntr
MP-168 AnlgCal Ref A
MP-169 AnlgCal Ref B
MP-184 LdJSVarCnt
MP-194 FbJSVarCnt
CP-381 Cmpr2 Parm
Enter a Monitor Parameter code in Compare 2 Parameter (CP-381) that will act on the value in Cmpr2 Val (CP-389), by
using the comparison type that you entered in Cmp2 Type (CP-385). If the comparison that is established by these three
parameters is “true”, then the PLC sets the Cmpr2 Out bit (61) in the PLC to “1”, which can be used to trigger a user
defined indicator.
Minimum Value: 1
Maximum Value: 199
Default Value: 33 (PosnErr)
Units: Parameter Code
NOTE: Refer to the "NOTE" in CP-380.
CP-382 Cmpr3 Parm
Enter a Monitor Parameter in Compare 3 Parameter (CP-382) that will act on the value in Cmpr3 Val (CP-390), by using the
comparison type that you entered in Cmp3 Type (CP-386). If the comparison that is established by these three
parameters is “true”, then the PLC sets the Cmpr3 Out bit (62) in the PLC to “1” , which can be used to trigger a user
defined indicator.
Minimum Value: 1
Maximum Value: 199
Default Value: 37 (CO Volts)
Units: Parameter Code
NOTE: Refer to the "NOTE" in CP-380.