Appendix C: Parameter Summary Numeric Quick Reference (continued)
CP-301 Acl Tm RUN
Acceleration Time RUN (CP-301) is the time that it takes to accelerate from 0 to the Ref Ramps (CP-300). Time is
consistant with Ref Ramps (CP-300) and Acl Rt RUN (CP-302).
Minimum Value: 0.5
Maximum Value: 3600
Default Value: 10.00
Units: Seconds
CP-302 Acl Rt RUN
Acceleration Rate RUN (CP-302) is the acceleration rate that the speed changes from 0 to the Ref Ramps (CP-300). Rate
is consistant with Ref Ramps (CP-300) and Acl Tm RUN (CP-301).
Minimum Value: 0
Maximum Value: 9999999
Default Value: 10.00
Units: Web EU/Tm/Sec
CP-303 Dcl Tm RUN
Deceleration Time RUN (CP-303) is the time that it takes to decelerate from Ref Ramps (CP-300) speed to 0. Time is
consistant with Ref Ramps (CP-300) and Dcl Rt RUN (CP-304).
Minimum Value: 0.5
Maximum Value: 3600
Default Value: 10.00
Units: Seconds
CP-304 Dcl Rt RUN
Deceleration Rate RUN (CP-304) is the deceleration rate that the speed changes from Ref Ramps (CP-300) speed to 0,
while operating in App Select (CP-202) 1, 2, 4 or 5. Rate is consistant with Ref Ramps (CP-300) and Dcl Tm RUN (CP-
303).
Minimum Value: 0
Maximum Value: 9999999
Default Value: 10.00
Units: Web EU/Tm/Sec
CP-305 Ramp Thd
When the difference between the ScaledRef (MP-30) and the RampedRef (MP-31) is greater than Ramp Thd (CP-
305), the ramp will work normally. When the difference between the ScaledRef (MP-30) and the RampedRef (MP-31) is
less than or equal to Ramp Thd (CP-305), the ramp will be bypassed. This avoids ramp delays for small speed changes
but still allows a ramp for large speed or for large Master SP (CP-210) changes.
Minimum Value: 0
Maximum Value: 999999
Default Value: 1.0
Units: EU/Tm
CP-310 Dcl Tm RStp
Deceleration Time R-Stop (CP-310) is the time, in seconds, that it takes to decelerate from the Ref Ramps (CP-300) speed
to 0, during R-Stop.
Minimum Value: 0.5
Maximum Value: 3600
Default Value: 10.00
Units: Seconds