Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5 - 10

Application Example: Equipment Protection

Using the /CLT Signal

The following section describes the use of the contact output signal /CLT as a torque
limit output signal.

This signal indicates whether servomotor output torque (current) is being limited.

Settings:

Pn402 (Forward Torque Limit)
Pn403 (Reverse Torque Limit)
Pn404 (Forward External Torque Limit): /P-CL input only
Pn405 (Reverse External Torque Limit): /N-CL input only

When the /CLT signal is used, the following parameter must be used to select the
output signal.

Output /CLT CN1-1

Torque Limit Output

Speed/Torque Control,

Position Control

Status

Conditions

Description

ON

The circuit between CN1-1 and 2 is

closed.

CN1-1 is at low level.

Servomotor output torque is being limited.

(Internal torque reference is greater than the

limit setting).

OFF

The circuit between CN1-1 and 2 is

open.

CN1-1 is at high level.

Servomotor output torque is not being limited.

(Internal torque reference is less than the limit

setting).

Parameter

Signal

Setting

Control Mode

Pn50F

Output Signal Selections 2

Default Setting: 0000

Speed/Torque Control,

Position Control

Motor

speed

Torque limit

Torque

Too small a torque limit will result in a

insufficient torque during acceleration and

deceleration.

Servo amplifier

CN1-1

CN1-2

CLT—

CLT+

I/O power supply

+24V

Photocoupler output levels per output node:
• Maximum operating voltage: 30V

DC

• Maximum output current: 50mA

DC