Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-134

For settings higher than 16384 P/R, pulses must be set in the following increments.

The setting error alarm A.09 (dividing ratio setting error) will occur if the setting is out-
side the allowable range or does not satisfy the setting conditions. The overspeed alarm
A.51 will occur if the motor speed exceeds the upper limit.
When setting the pulse dividing ratio using a digital operator or panel operator, the display
of the number of pulses increments as shown in the above table and the upper limit will
not increment above the resolution of mounted encoder.
When Pn212 is set without connecting a servomotor to the servo amplifier, the upper limit
is automatically set to 2

30

(=1073741824: the maximum output value of the sero ampli-

fier) since the encoder resolution of the servomotor is unknown.
Therefore, it is recommended to set Pn212 after connecting a servomotor.

Encoder Resolution

(Bits)

Number of Encoder

Pulses per Revolution

(P/R)

Setting Range

(P/R)

13

2048

16 to 2048

Pn212 needs not be

used.

16

16384

16 to 16384

17

32768

16 to 32768

20

262144

16 to 262144

PG Dividing Pulse

Setting (P/R)

Increments

(P/R)

Motor Speed Upper Limit

(rpm)

16 to 16384

1-pulse

No limit (up to the motor maximum

speed)

16386 to 32768

2-pulse

82×10

6

/Set value

32772 to 65536

4-pulse

65544 to 131072

8-pulse

131088 to 262144

16-pulse