Example of i/o signal generation timing, Reference pulse input signal timing – Yaskawa Sigma II Series Servo System User Manual
Page 106

Sigma II User’s Manual
Chapter 5: Parameter Settings and Functions
5 - 20
Example of I/O Signal Generation Timing
Note: 1. In order for the input pulse to register, the interval from the time the servo ON signal is turned
ON until a reference pulse is entered must be a minimum of 40ms.
2. The error counter clear signal must be on for at least 20
μs.
Reference Pulse Input Signal Timing
Reference Pulse Form
Electrical Specifications
Sign + pulse train input
(SIGN + PULS signal)
Maximum reference
frequency: 500kpps
(200kpps open-collector
output)
t1, t2
≤ 0.1µs
t3, t7
≤ 0.1µs
t4, t5, t6 > 3µs
τ ≥ 1.0µs
(
τ/T) × 100 ≤
50%
Sign (SIGN)
H = Forward reference
L = Reverse reference
CW pulse and CCW
pulse
Maximum reference
frequency: 500kpps
(200kpps open-collector
output)
t1, t2
≤ 0.1µs
t3 > 3µs
τ ≥ 1.0µs
(
τ/T) × 100 ≤
50%
—
Two-phase pulse train
with 90
° phase differential
(A phase + B phase)
Maximum reference
frequency
×
1: 500kpps
(200kpps open-collector
output)
×
2: 400kpps
×
4: 200kpps
t1, t2
≤ 0.1µs
τ ≥ 1.0µs
(τ/T) × 100 =
50%
Parameter Pn200.0 is
used to switch the
input pulse multiplier
mode.
Servo ON
Baseblock
Sign+pulse
train
Release
PG pulse
CN1-1
1
CN1-
7
PAO
PBO
t6
t1
≤ 30ms
t2
≤ 6ms
(when parameter
Pn506 is set to 0)
t3
≥ 40ms
t4, t5, t6
≤ 2ms
t
7 ≥ 20ms
CN1-11
CN1-7
t7
t2
t1
t3
t4
t5
t6
T
τ
Forward
reference
Reverse
reference
SIGN
PULS
Forward
reference
Reverse
reference
t2
t1
t3
T
τ
CCW
CW
Forward
reference
Reverse
reference
t2
t1
T
τ
A phase
B phase
B phase leads
A phase by 90°
B phase lags
A phase by 90°