Chapter 5: Parameter Settings and Functions

5-73

5.5.2

Using the Servo ON Input Signal (/S-ON)

The basic use and wiring procedure for the Servo ON (/S-ON) input signal
(sequence input signal) is described below. Use this signal to forcibly turn OFF the
servomotor from the host controller.

This signal is used to turn the servomotor ON and OFF.

Set the following parameter to 7 if the /S-ON signal will not be used.

Input /S-ON CN1-40

Servo ON

Speed/Torque Control,

Position Control

CN1-40

State

Status

Result

ON

Closed or low level

Turns ON the servomotor: operates

according to signal input.

This is the default state.

OFF

Open or high level

Servomotor cannot operate.

Do not turn OFF the servomotor while it is

operating except in an emergency.

Do not use the Servo ON (/S-ON) signal to start or stop the motor. Always use an input reference

signal, such as Speed Reference to start or stop the servomotor.

Doing so will shorten the life of the servo amplifier.

Parameter

Signal

Setting

Description

Pn50A.1

/S-ON Signal Mapping

Default Setting: 0

Speed/Torque Control,

Position Control

+24V

CN1-47

CN1-40

7mA

0V

Servo amplifier

I/O power supply

Photo

coupler

Host controller

/S-OUT

+24V

IN

3.3k

Ω

CAUTION

Servo amplifier

0V

CN-40
(/S-ON)

The external short-circuit wiring shown

in the figure can be omitted if the Servo ON

(/S-ON) input is not used.