2 connection cables, 6wiring, 3 wiring guidelines – Pilz PMCtendo DD5.03/000/0/0/0/110-230VAC User Manual
Page 98

6.3
Wiring guidelines
6
Wiring
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-8
6.3.2
Connection cables
Connection cables
6-
][Verdr_Leiterquerschnitte_DD5
Single-axis systems
We recommend the following cable cross sections in accordance with
EN 60204:
* North America: max. 39 m length, Europe: up to max. length
Connection
Pin designation
Cable cross section
Conditions
Mains voltage AC
X0
1.5 mm²
600 V
DC intermediate circuit
Brake resistor
X8
1.5 mm²
1000 V, shielded for lengths
> 20 cm
Motor cables without
choke, max. 25 m
X9
1.5 mm²
600 V, shielded,
C < 150 pF/m
Motor cables with choke, 25
– 50 m*
X9
1 mm²
600 V, shielded,
C < 150 pF/m
Resolver, thermal switch,
max.100 m*
X2
4x2x0.25 mm²
Twisted pair,
shielded, C < 120 pF/m
Encoder, thermal switch,
Max. 50 m*
X1
7x2x0.25 mm²
Twisted pair, shielded
Incremental encoder, ther-
mal switch,
Max. 25 m
X1
8x2x0.25 mm²
Twisted pair, shielded
Analogue inputs, AGND,
max 30 m
X3
0.25 mm²
Twisted pair, shielded
Digital inputs and outputs,
BTB, DGND, max. 30 m
X3
0.5 mm²
Holding brake (motor):
X9
Min. 0.75 mm
2
600 V, shielded, check volt-
age drop
+24 V/DGND
X4
Max. 2.5 mm²
Check voltage drop