6 communication interfaces, 1 rs232 interface, 6wiring – Pilz PMCtendo DD5.03/000/0/0/0/110-230VAC User Manual
Page 146: 7 control element

6.7
Control element
6
Wiring
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-56
6.7.6
Communication interfaces
Communication interfaces
6-
6.7.6.1
RS232 interface
RS232 interface
6-
][Verdr_RS_232_protego_D
We recommend shielded cable for the RS232 interface.
If you use unshielded cables, the interface may malfunction.
Earth the cable shield connection at both ends (e.g. on a bus bar).
Transient currents can be anticipated on longer cables. If this is the
case you should use equipotential bonding cables.
With the supply voltages switched off, connect the interface (X6) on
the servo amplifier to a serial interface on the PC via a null modem ca-
ble.
INFORMATION
Do not use a null modem link cable!
Connector pin assignment
Connector X6
Pin
Designation
Description
2
RxD
Receive data
3
TxD
Send
d
ata
5
GND
Earth
Connection
Interface
RS232
Shielded cable
Shield connection on a bus bar
The interface is on the same connec-
tor as the CANopen interface.
The RS232 and CANopen interface
use the same operating earth (GND).
1
5
6
9
RxD
2
3
Servo Drive
X6
TxD
PC
5
GND
TxD
RxD
GND