RS232 interface

RS232 interface

6-

][Verdr_RS_232_protego_D

We recommend shielded cable for the RS232 interface.

If you use unshielded cables, the interface may malfunction.

Earth the cable shield connection at both ends (e.g. on a bus bar).

Transient currents can be anticipated on longer cables. If this is the
case you should use equipotential bonding cables.

With the supply voltages switched off, connect the interface (X6) on
the servo amplifier to a serial interface on the PC via a null modem ca-
ble.

INFORMATION
Do not use a null modem link cable!

Connector pin assignment

Connector X6

Pin

Designation

Description

2

RxD

Receive data

3

TxD

Send

d

ata

5

GND

Earth

Connection

Interface

RS232

Shielded cable

Shield connection on a bus bar

The interface is on the same connec-
tor as the CANopen interface.

The RS232 and CANopen interface
use the same operating earth (GND).

1

5

6

9

RxD

2

3

Servo Drive

X6

TxD

PC

5

GND

TxD

RxD

GND