6.8.2
Expansion card for PROFIBUS-DP interface
Expansion card for PROFIBUS-DP interface
6-
][Verdr_PROFIBUS_protego_D
Connector pin assignment
Connector X12A/X12B
Pin
Designation
Description
1
n. c.
--
2
n. c.
--
3
RxD/TxD-P
B-line
4
n. c.
--
5
GND
Earth
6
VP
Supply voltage +5 VDC
7
n. c.
--
8
RxD/TxD-N
A-line
n. c. = not connected
Connection
Interface
PROFIBUS-DP
Shielded cable
Shield connection in the connector
INFORMATION
Cable selection, cable routing, shielding, bus connectors, bus
termination and runtimes are all described in the “PROFIBUS-
DP/FMS Installation Guidelines” published by the PROFIBUS
User Group PNO.
1
5
6
9
1
4
6
Servo Drive
PLC
3
A (RxD/TxD-N)
GND
VP
390 W
390 W
390 W
220 W
220 W
390 W
5
8
1
4
6
3
5
8
B (RxD/TxD-P)
A (RxD/TxD-N)
GND
VP
B (RxD/TxD-P)
X12A
X12B