beautypg.com

4 expansion card for devicenet, 6wiring, 8 expansion cards – Pilz PMCtendo DD5.03/000/0/0/0/110-230VAC User Manual

Page 154

background image

6.8

Expansion cards

6

Wiring

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-64

6.8.4

Expansion card for DeviceNet

Expansion card for DeviceNet

6-

][Verdr_DeviceNet_protego_D

When installing and wiring please refer to the “DeviceNet Specification,
Volume I, II, Version 2.0”, published by ODVA. This contains information
on:

Cable selection

Cable routing

Shielding

Bus connectors

Bus termination

Runtimes

Correct wiring:

Stub lines of 0 ... 6 m are permitted on each device.

Branches within stub lines are permitted.

Voltage to the devices can be supplied via the bus

INFORMATION
Please note:
The signal lines on the first and last subscribers should use con-
nectors fitted with terminating resistors in accordance with the
“DeviceNet Specification, Vol I, Chapter 9” (from Version 2.0,
1997): 121 Ohm, 1% metal film, 1/4 Watt.

Connector pin assignment

Connector X15

Pin

Designation

Description

1

V-

Supply voltage (-)

2

CAN_L

DeviceNet connection (low signal)

3

SHIELD

Cable shield connection

4

CAN_H

DeviceNet connection (high signal)

5

V+

Supply voltage (+)

5-pin Combicon plug-in connector in accordance with the DeviceNet specification

X15 1 2 3 4 5