7-15

7.4

Messages/errors

7

Commissioning

* = These warning messages result in a controlled shutdown of the drive
(braking with emergency ramp).

n10*

PSTOP

PSTOP limit switch operated

n11*

NSTOP

NSTOP limit switch operated

n12

Motor default values
loaded

ENDAT or HIPERFACE® only: Discrepancy
between the motor numbers saved in the en-
coder and amplifier, motor default values have
been loaded.

n13*

Expansion card

Problem with the 24V supply for the I/O ex-
pansion card

n14

SinCos feedback

SinCos commutation (wake & shake) incom-
plete, will be cleared if amplifier is enabled and
wake & shake is executed

n15

Table error

Fault as per speed/current table INXMODE 35

n16

Summary warning

Summary warning for n17 to n31

n17

Fieldbus Sync

CAN Sync is not logged in

n18

Multi-turn overflow

Maximum number of rotations exceeded

n19

Ramp restricted on
motion block

Value range exceeded for motion block data

n20

Invalid motion block

Invalid motion block

n21

Warning through
PLC program

Refer to PLC program

n22

Motor temperature
exceeded

The warning gives the user options for how to
respond before the "motor temperature" error
causes a controller shutdown.

n23

Sine/cosine encoder Warning threshold reached

n24

Digital inputs

Illogical configuration

n25-
n31

Reserved

Reserved

n32

Firmware beta ver-
sion

Firmware version has not been released

No.

Error message