4.2

Power element

4

Function description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-4

Connection via isolating transformer

400 – 480 V mains supplies without earthed star point (asymmetrically
earthed or unearthed mains supplies), see Fig. (7) – (11)

Requirements for isolating transformers

An earthed star point must be available on the secondary side. The
star point on the secondary side must be earthed and must be con-
nected to the servo amplifier's protective earth conductor. This will
prevent overvoltages between the external conductors and the servo
amplifier housing.

The isolating transformers must have the relevant input and output
voltages.

The following illustration shows the connection types.