5 installation, General requirements, 5installation – Pilz PMCtendo DD5.03/000/0/0/0/110-230VAC User Manual
Page 85: 1 general requirements
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
5-1
5.1
General requirements
5
Installation
55000
Installation
Installation
5-
5.1
General requirements
5100
General requirements
5-
][Montage_Einbauort
Mounting location
The servo amplifier should be installed in an enclosure, e.g. control
cabinet, that conforms to the protection class required for the envi-
ronment.
The mounting location must be free from conductive and aggressive
materials.
Make sure you keep the necessary space clear above and below the
servo amplifier (see section entitled “Installing the servo amplifier”)
][Montage_Umgebung
Environmental conditions
When installing the system in an enclosure such as a control cabinet,
the environmental data for the servo amplifier must be taken into ac-
count. Details can be found in the chapter entitled “Technical Details”.
Protect the servo amplifier from undue stress. In particular, do not al-
low any components to become bent and/or insulation distances to
be modified during transportation and handling.
Make sure there is an adequate flow of cool, filtered air from the bot-
tom of the control cabinet or use a heat exchanger. Please note the
ambient temperature of
0 - 40 °C with nominal data, 40 - 55 °C with
power derating
2.5 %/K.
In extreme ambient conditions, additional measures may be required
in order to keep within the prescribed value range.
][Montage_Erdung
Earthing, EMC
Make sure that the servo amplifier and motor are earthed correctly.
Do not use varnished (non-conductive) mounting plates.
Components that generate magnetic fields should not be installed di-
rectly next to the servo amplifier. If necessary, shield the magnetic
fields.
][Montage_Entladung
Damage due to electrostatic discharge!
Electrostatic discharge can damage components. Ensure discharge
before touching the servo amplifier, e.g. by touching an earthed, con-
ductive surface or by wearing an earthed armband.
][Montage_Netzteil
Power supply
The servo amplifier and power supply should be installed close to
each other on the conductive,
earthed mounting plate inside the con-
trol cabinet.
][Montage_Schaltschrankbeleuchtung
Control cabinet lighting
Use low interference panel lighting for inside the control cabinet.