Elecraft K2 Owner's Manual User Manual
Page 65
64
E
LECRAFT
®
VCO Alignment
In the following steps you’ll adjust the VCO inductor (L30) so that the
VCO control voltage is in the proper range.
Disconnect the internal frequency counter probe and remove it
completely from the K2.
Select 80 meters, and set the VFO for about 4000 kHz.
Connect a DMM (digital multimeter) to the left end of resistor
R30 (near the center of the synthesizer area of the RF board) and
ground. Use a small alligator clip to ensure a good connection. (You
can also use the built-in voltmeter to measure the VCO control
voltage. Refer to Voltmeter Probe Assembly in Part I.)
It is possible to damage the slugs in slug-tuned inductors if
you use a metal tool or if you tune the slug too far in or out. The
tuning tool provided will not damage the slugs.
Using the wide end of the plastic tuning tool, adjust the slug in
inductor L30 until the voltage at R30 reads 6.0 V. If the voltmeter
reading does not change at all as you tune L30 through its full range,
refer to Troubleshooting. If the voltage changes but you cannot get to
6.0 V, you have probably wound the VCO inductor (T5) incorrectly or
have installed the wrong value at L30 or C72.
Set the VFO for approximately 3500 kHz.
Measure and write down the VCO control voltage at this
frequency in Table 6-1 (using pencil).
For each remaining band, set the VFO to the low and high
frequencies listed in Table 6-1 and write down the VCO control
voltages.
9
(You can tune quickly to the approximate frequencies in the
table by selecting the 1-kHz tuning rate.)
9
Usable VFO coverage extends well beyond the ranges given in the table. 15 MHz is
used as the upper boundary on 20 meters to allow reception of WWV at this
frequency.
Table 6-1. VCO Voltage Readings
Band Low
Freq.
Voltage
High Freq. Voltage
80
m
3500
______
4000
______
40
m
7000
______
7300
______
30
m
10000
______
10150
______
20
m
14000
______
15000
______
17
m
18000
______
18200
______
15
m
21000
______
21450
______
12
m
24800
______
25000
______
10
m
28000
______
28800
______
If some VCO control voltage readings above are < 1.5 V, or
some of them are > 7.5 V, you may be able to shift the entire set of
readings so that they are all within the 1.5 to 7.5 V range. Switch to
the band (and frequency) that had the highest or lowest voltage, then
adjust L30 to bring that reading into range. Then re-measure all of the
voltages to make sure they're in range.
i
If you have some voltages that are < 1.5 V and others that are
> 7.5 V, you have probably installed the wrong value at one or more of
the VCO capacitors (C71-C74) or varactor diodes (D21-D26). Another
possibility is that T5 has the wrong number of turns or that you
installed the wrong type of slug-tuned inductor at L30. If you change
any of these components, repeat the VCO alignment procedure.
Disconnect the DMM from R30.
Connect the internal frequency counter probe to the BFO test
point, TP2 (right side of the RF board, near the crystal filter).
i