beautypg.com

Operator’s manual – Great Plains DICKEY-john IntelliAg Planter-Drill Control L3 User Manual

Page 88

background image

OPERATOR’S MANUAL

IntelliAg PDC User 2 & 3

11001-1501-200811

80 / SYSTEM CONFIGURATION

5. Run the engine at normal operating speed until the hydraulic fluid is at

normal operating temperature.

6. Press the Start button.
7. Turn the master switch to the ON position.
8. The valve calibration will immediately start.
9. Keep the hydraulics engaged until the calibration is complete. The

calibration may take a minute up to several minutes. Each calibration
step is monitored on the lower left corner of the display.

10. When the calibration is complete, the control shuts down automatically.

All calibration data is automatically stored.

LIMIT OUTPUT

In certain instances, it is necessary to limit the output of the control channel.
System capacities are greater than the actual desired capacities. These
features allow you to set the maximum output of the channel to prevent
machine damage.

1. Press the Limit Output button to access the Limit Output screen.

NOTE: If the Channel is turned OFF,

the Increment, Decrement, and
Reset buttons will not function.
Return to the Main Work screen
to turn ON.

Figure 49
Limit Output Screen

To Limit Max Output:

1. Move the implement to the “raised” position.
2. Apply the tractor brakes and lock in the applied position.
3. Put the transmission in “park” or in a locked, neutral position.
4. Start the tractor and engage PTO if used to drive the hydraulic system.
5. Run the engine at normal operating speed until the hydraulic fluid is at

normal operating temperature.

6. Place the master switch in the ON position.
7. To change the valve position, press the Increment or Decrement

buttons repeatedly until the desired minimum or maximum output value
is reached.

8. Press the Start button and the valve calibration will immediately begin.

The calibration will run using the new max flow value.

This manual is related to the following products: