beautypg.com

Operator’s manual, Troubleshooting & alarms / 167 – Great Plains DICKEY-john IntelliAg Planter-Drill Control L3 User Manual

Page 175

background image

OPERATOR’S MANUAL

IntelliAg PDC User 2 & 3

11001-1501-200811

TROUBLESHOOTING & ALARMS / 167

227

RPM Sensor Low Limit
Exceeded Alarm

SENSED RPM BELOW THE LOW ALARM
SETTING ON THE RPM SETUP SCREEN.
1. Implement malfunction or incorrect
setup.
2. Defective RPM sensor.

3. Defective module harness or module.

1. Verify proper implement operation/setup.

2. Inspect RPM sensor for damage.
Replace if necessary.
3. Inspect module for damage. Replace if
necessary.

228

Hopper Sensor Detection
Alarm

NUMBER OF HOPPER SENSORS
CONNECTED DOES NOT AGREE WITH
THE NUMBER OF SENSORS
CONFIGURED ON THE HOPPER
SENSOR CONFIGURATION SCREEN.
1. Defective hopper sensor.

2. Defective module or damaged module
harness.
3. Additional hopper sensors detected.

1. Inspect hopper sensor for damage or
replace.
2. Inspect module and/or module harness
for damage. Replace if necessary.
3. Verify correct # HOPP setting for each
module.

229

Hopper Sensors Installed
Incorrectly Alarm

HOPPER SENSORS ARE NOT
INSTALLED SEQUENTIALLY ON A
MODULE.
1. Incorrect hopper sensor connections.

2. Defective hopper sensor.

3. Defective module or damaged module
harness.

1. Verify hopper sensors are connected
sequentially on all modules as instructed in
INSTALLATION.
2. Inspect hopper sensor for damage or
replace.
3. Inspect module and/or module harness
for damage. Replace if necessary.

230

Pressure Sensors
Installed Incorrectly Alarm

PRESSURE SENSORS ARE NOT
INSTALLED SEQUENTIALLY ON A
MODULE.
1. Incorrect pressure sensor connections.

2. Defective pressure sensor.

3. Defective module or damaged module
harness.

1. Verify pressure sensors are connected
sequentially on all modules as instructed in
INSTALLATION.
2. Inspect pressure sensor for damage or
replace.
3. Inspect module and/or module harness
for damage. Replace if necessary.

231

Seeding Detected on a
Tramlined Row Alarm

Occurs if a tramlined row does not shut off
the row unit and seeds continue to be
detected. (Only possible if system supports
tramlining).
1. Output to row mapping is assigned
incorrectly.
2. Seed sensor malfunction.

1. Check output row mapping.
2. Check seed sensor to ensure no false
triggering.
3. Inspect and verify Tramline output is
shutting off seeds correctly.

232

RPM Sensor Low Limit
Exceeded With Control
Channel Shutdown Alarm

RPM HAS DROPPED BELOW THE
DISABLE CONTROL ON LOW ALARM
SETTING ON THE ACCESSORY SETUP
SCREEN.
1. Defective RPM sensor.

2. Damaged module harness.

3. Defective module.

4. Low RPM

1. Inspect RPM sensor for damage.
Replace if necessary.
2. Inspect module harness for damage.
Repair or replace.
3. Inspect module for damage. Replace if
necessary.
4. Increase RPM.

ALARM
#

ALARM

PROBABLE CAUSE

CORRECTIVE ACTION

This manual is related to the following products: