Operator’s manual, Troubleshooting & alarms / 167 – Great Plains DICKEY-john IntelliAg Planter-Drill Control L3 User Manual
Page 175
OPERATOR’S MANUAL
IntelliAg PDC User 2 & 3
11001-1501-200811
TROUBLESHOOTING & ALARMS / 167
227
RPM Sensor Low Limit
Exceeded Alarm
SENSED RPM BELOW THE LOW ALARM
SETTING ON THE RPM SETUP SCREEN.
1. Implement malfunction or incorrect
setup.
2. Defective RPM sensor.
3. Defective module harness or module.
1. Verify proper implement operation/setup.
2. Inspect RPM sensor for damage.
Replace if necessary.
3. Inspect module for damage. Replace if
necessary.
228
Hopper Sensor Detection
Alarm
NUMBER OF HOPPER SENSORS
CONNECTED DOES NOT AGREE WITH
THE NUMBER OF SENSORS
CONFIGURED ON THE HOPPER
SENSOR CONFIGURATION SCREEN.
1. Defective hopper sensor.
2. Defective module or damaged module
harness.
3. Additional hopper sensors detected.
1. Inspect hopper sensor for damage or
replace.
2. Inspect module and/or module harness
for damage. Replace if necessary.
3. Verify correct # HOPP setting for each
module.
229
Hopper Sensors Installed
Incorrectly Alarm
HOPPER SENSORS ARE NOT
INSTALLED SEQUENTIALLY ON A
MODULE.
1. Incorrect hopper sensor connections.
2. Defective hopper sensor.
3. Defective module or damaged module
harness.
1. Verify hopper sensors are connected
sequentially on all modules as instructed in
INSTALLATION.
2. Inspect hopper sensor for damage or
replace.
3. Inspect module and/or module harness
for damage. Replace if necessary.
230
Pressure Sensors
Installed Incorrectly Alarm
PRESSURE SENSORS ARE NOT
INSTALLED SEQUENTIALLY ON A
MODULE.
1. Incorrect pressure sensor connections.
2. Defective pressure sensor.
3. Defective module or damaged module
harness.
1. Verify pressure sensors are connected
sequentially on all modules as instructed in
INSTALLATION.
2. Inspect pressure sensor for damage or
replace.
3. Inspect module and/or module harness
for damage. Replace if necessary.
231
Seeding Detected on a
Tramlined Row Alarm
Occurs if a tramlined row does not shut off
the row unit and seeds continue to be
detected. (Only possible if system supports
tramlining).
1. Output to row mapping is assigned
incorrectly.
2. Seed sensor malfunction.
1. Check output row mapping.
2. Check seed sensor to ensure no false
triggering.
3. Inspect and verify Tramline output is
shutting off seeds correctly.
232
RPM Sensor Low Limit
Exceeded With Control
Channel Shutdown Alarm
RPM HAS DROPPED BELOW THE
DISABLE CONTROL ON LOW ALARM
SETTING ON THE ACCESSORY SETUP
SCREEN.
1. Defective RPM sensor.
2. Damaged module harness.
3. Defective module.
4. Low RPM
1. Inspect RPM sensor for damage.
Replace if necessary.
2. Inspect module harness for damage.
Repair or replace.
3. Inspect module for damage. Replace if
necessary.
4. Increase RPM.
ALARM
#
ALARM
PROBABLE CAUSE
CORRECTIVE ACTION