Lenze EVF9383 User Manual
Page 87
Basic devices in the power range 250 ... 400 kW
Master and slave connection
5.5
5.5.2
l
5.5−5
EDSVF9383V EN 7.1−04/2012
Connection of the control cables between master and slave
DC+
DC-
0
2
1
1
0
4
0
5
1
3
9300VEC028
Fig. 5.5−4
Connection of the control cables between master and slave
1. Installation and connection of the ribbon cable
0:
By default the ribbon cable is inside the master. The plug
2 is already
attached to the Drive Board.
– Route the ribbon cable from the master to the Drive Board
connection in the slave, inserting the ribbon cable into the cable
ducts
1.
– Plug the ribbon cable plug
0 into the socket 3 at the Drive Board.
2. Laying and connecting 2−core cables with plugs
4:
By default the cable is inside the master. The corresponding cable with
socket is in the slave.
– Lay the two−core cable from the master to the socket in the slave.
– Connect the 2−pole plug with the 2−pole socket in the slave.
3. Laying and connecting 10−core cables with plugs
5:
By default the cable is inside the master. The corresponding cable with
socket is in the slave.
– Lay the two−core cable from the master to the socket in the slave.
– Connect the 10−pole plug with the 10−pole socket in the slave.
How to connect the control
cables