2 resetting system error messages, Resetting system error messages, Troubleshooting and fault elimination – Lenze EVF9383 User Manual
Page 399
Troubleshooting and fault elimination
System error messages
Resetting system error messages
9.5
9.5.2
l
9.5−5
EDSVF9383V EN 7.1−04/2012
Remedy
Cause
Description
Fault message
Remedy
Cause
Description
Display
No.
0140
ID1
Error during motor data
identification.
No motor connected.
Check motor connection.
Stator resistance too high.
Check entered motor data.
Controller inhibited externally.
Enable controller and repeat
motor data identification. The
controller enable must be
pending continuously until the
end of the identification process.
0141
ID2
Error during motor data
identification.
Motor too small.
l
Check entered motor data. For
parameterisation with Global
Drive Control, use the input
assistant for motor data.
l
The measurements for the
inverter error characteristic
and the stator resistance are
correct (save measured values
in C0003). For the operating
mode V/f characteristic control
the motor data identification
can be completed.
Controller inhibited externally.
Enable controller and repeat
motor data identification. The
controller enable must be
pending continuously until the
end of the identification process.
x200
NMAX
Maximum system speed (C0596)
has been exceeded.
l
Active load (e.g. for hoists) is
too high.
l
Drive is not speed−controlled,
torque is excessively limited.
l
Check drive dimensioning.
l
Increase torque limit, if
necessary.
l
Switch off monitoring
(C0607 = 3).
Representation of the error number:
x
0 = TRIP, 1 = message, 2 = warning
E. g. "2091": An external monitoring function has triggered EEr warning
9.5.2
Resetting system error messages
Response
Measures for resetting the fault message
TRIP
Note!
If a TRIP source is still active, the pending TRIP cannot be reset.
Resetting the TRIP can be effected by:
l
Pressing the keypad XT EMZ9371 BC
ð S. Then press U to re−enable the controller.
l
Setting code C0043 = 0.
l
Control word C0135, bit 11
l
Control word AIF
l
Control word of system bus (CAN)
After resetting the TRIP, the drive remains at standstill.
Message
Danger!
After elimination of the fault, the fault message is cancelled automatically and the drive restarts
automatically.
Warning
After elimination of the fault, the fault message is cancelled automatically.