Code table
8.5
l
8.5−3
EDSVF9383V EN 4.0−03/2006
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0010 N
min
0
0
{1 rpm}
36000
l
Reference value
for the absolute
and relative
setpoint selection
for the
acceleration and
deceleration
times
l
C0059 must be
set correctly
l
Set C0010 <
C0011
l
C0010 is only
effective in case
of analog setpoint
selection via AIN1
Important: For
parameter setting
via interface, major
changes in one step
should only be made
when the controller
is inhibited.
Minimum
speed
^
6.10−1
C0011 N
max
3000 0
{1 rpm}
36000
Maximum
speed
C0012 Tir (acc)
5.00
0.00
{0.01 s}
9999.90 Acceleration time T
ir
of the main
setpoint
l
Refers to speed change
0 ... C0011
^
6.10−3
C0013 Tif (dec)
5.00
0.00
{0.01 s}
9999.90 Deceleration time T
if
of the main
setpoint
l
Refers to speed change
0 ... C0011
C0014 V/f charact.
0
Characteristic in the V/f
characteristic control mode
^
8.2−25
0
Linear
Linear V/f characteristic
1
square
Square V/f characteristic
C0015 Rated freq
50
10
{1 Hz}
5000 V/f−rated frequency
In C0015 you can set a base
frequency which differs from the
rated motor frequency (C0089)
l
Lenze setting: C0015 = C0089
l
Changing C0086 or C0089
overwrites the value in C0015
^
8.2−25
C0016 Umin boost
0.00
0.00
{0.01 %}
100.00 U
min
boost (FCODE)
l
C0016 = 1 % corresponds to a
boost of 1 % of the rated motor
voltage (C0090)
l
Code is freely configurable
^ 6.8−4
C0017 FCODE (Qmin)
50
−36000
{1 rpm}
36000 Q
min
−switching threshold (FCODE)
l
Programmable speed threshold
l
If the current speed is < C0017,
CMP1−OUT is activated.
l
Freely configurable code