Basic devices in the power range 110 ... 200 kW
Motor connection
5.4
5.4.7
l
5.4−7
EDSVF9383V EN 7.1−04/2012
5.4.7
Motor connection
ƒ To comply with the EMC regulations, Lenze recommends to use
shielded motor cables.
ƒ Shield clamps are not included in the scope of supply.
(
Stop!
The user is responsible for sufficient strain relief!
BR2
BR1
PE
U
V
W
40 mm
PE
15-20 Nm
M6
133-176 lb-in
U, V, W
25-30 Nm
M8
221-264 lb-in
0
max.
300 mm
1
9300VEC005
Fig. 5.4−6
Motor connection example
BR1, BR2 Brake resistors can only be operated with variants V060, V110, V270
and V300
0
Connect the motor cable shield with a surface as large as possible to
the control cabinet mounting plate by using the clamps.
1
Conductive surface
Ensure to have the poles right!
Do not exceed the maximum motor cable length!
9300 vector
Installation in accordance with EN 60204−1
U, V, W
PE
Type
[mm
2
]
[mm
2
]
EVF9335−EV
EVF9335−EVVxxx
150
2 × 50
1)
95
EVF9336−EV
EVF9336−EVVxxx
150
2 × 50
1)
95
EVF9337−EV
EVF9337−EVVxxx
150
2 × 50
1)
95
EVF9338−EV
EVF9338−EVVxxx
240
2 × 95
1)
150
1)
Two conductors per path; both conductors must have the same
cross−section
Observe the national and regional legislation
Cable cross−section