3 with function "safe torque off" active, With function "safe torque off" active – Lenze EVF9383 User Manual

Page 102

background image

Control terminals
With function "Safe torque off" active

5.6
5.6.3

l

5.6−4

EDSVF9383V EN 7.1−04/2012

5.6.3

With function "Safe torque off" active

ƒ The installation and commissioning of the Safe torque off" function

must be carried out by skilled personnel only.

ƒ All safety−relevant cables (e.g. control cable for the safety relay,

feedback contact) outside the control cabinet must be protected, for
instance by a cable duct. Short circuits between the single cables must
be ruled out!

ƒ Wiring of the safety relay K

SR

with insulated wire end ferrules or rigid

cables is absolutely vital.

ƒ The electrical reference point for the coil of the safety relay K

SR

must be

connected with the protective conductor system (DIN EN 60204−1
paragraph 9.4.3). Only this measure guarantees that the operation is
protected against earth faults.

I

Tip!

A complete description can be found in the chapter "Safe torque
off".

Safety instructions for the
installation of the "Safe
torque off" function