Configuration, Code table – Lenze EVF9383 User Manual
Page 348
Configuration
Code table
8.5
l
8.5−60
EDSVF9383V EN 4.0−03/2006
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0970
s
CFG: SET
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MFAIL
l
Starting value for the
controlled deceleration in [%]
of C0011
See System
Manual
(extension)
C0971
s
CFG: FAULT
1000 FIXED0
^ Selection list 2
Configuration of digital input
signal, function block MFAIL
l
HIGH = activates mains failure
control
C0972
s
CFG: RESET
1000 FIXED0
^ Selection list 2
Configuration of digital input
signal, function block MFAIL
l
HIGH = resets mains failure
control
C0973
s
CFG: ADAPT
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MFAIL
l
Dynamic adaptation of the
proportional gain of U
Gsetl
controller in [%] of C0980
C0974
s
CFG: CONST
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MFAIL
l
Proportional gain of U
Gset
controller in [%] of C0980
C0975
s
CFG:
THRESHLD
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MFAIL
l
Restart protection when the
value falls below the speed
threshold
l
Restart threshold in [%] of
C0011
C0976
s
CFG: NACT
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MFAIL
l
Comparison value for the
restart threshold in [%] of
C0011
l
Start for V
2
controller
C0977
s
CFG: SET
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MFAIL
l
Speed starting value for the
deceleration in [%] of C0011
C0978
s
CFG: DC−SET
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MFAIL
l
Setting of the voltage setpoint
on which the DC−bus voltage is
to be kept (100 % = 1000 V)
C0980 MFAIL Vp
0.500 0.001
{0.001}
31.000 Gain V
p
, function block MFAIL
See System
Manual
(extension)
C0981 MFAIL Tn
100
20
{1 ms}
2000 Integral−action time T
n
, function
block MFAIL
C0982 MFAIL Tir
2.000 0.001
{0.001 s}
16.000 Acceleration time T
ir
, function
block MFAIL
C0983 Retrigger T
1.000 0.001
{0.001 s}
60.000 Retrigger time, function block
MFAIL
l
After the time has elapsed, the
mains failure control is
terminated