3 free configuration of analog input signals, Free configuration of analog input signals – Lenze EVF9383 User Manual
Page 138
Changing the assignment of the control terminals X5 and X6
Free configuration of analog input signals
6.5
6.5.3
l
6.5−4
EDSVF9383V EN 7.1−04/2012
6.5.3
Free configuration of analog input signals
ƒ Internal analog signals can be freely linked with external analog signal
sources:
– Analog inputs X3/1, X3/2 and X3/3, X3/4
ƒ One signal source can be linked with several targets.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0026
−199.99
{0.01 %}
199.99 Free control code FCODE 26/1 and
FCODE26/2
^
6.5−4
See System
Manual
(extension)
1 FCODE (offset)
0.00
Offset of AIN1 (X6/1, X6/2)
2 FCODE (offset)
0.00
Offset of AIN2 (X6/3, X6/4)
C0027
−199.99
{0.01 %}
199.99 Free control code FCODE 27/1 and
FCODE27/2
1 FCODE (gain)
100.0
0
Gain AIN1 (X6/1, X6/2)
l
100 % = gain 1
2 FCODE (gain)
100.0
0
Gain AIN2 (X6/3, X6/4)
l
100 % = gain 1
C0034 Mst current
0
0
−10 V ... +10 V
Voltage / current range for analog
signals at input X6/1, X6/2
l
Observe jumper position of X3
^ 5.6−9
^
6.5−4
1
4 mA ... 20 mA
2
−20 mA ... +20 mA
The internal analog signals can be linked with an external signal source by
entering the selection figure of the external signal into the configuration
code of the internal analog signal.
Example
ƒ C0780 = 50
ð signal source for the main setpoint (NSET−N) is terminal
X6/1, X6/2
NSET
C0046
NSET-N
DMUX
0
3
0
15
NSET-JOG*1
NSET-JOG*2
NSET-JOG*4
NSET-JOG*8
C0780
C0787/1
C0787/2
C0787/3
C0787/4
C0034
1
2
AIN1
+
+
AIN1-OUT
AIN1-GAIN
AIN1-OFFSET
C0404/1
C0404/2
C0402
C0403
C0400
X6
C0010
+
+
9300vec106
Fig. 6.5−2
Linking analog signal NSET−N with terminal X6/1, X6/2
I
Tip!
ƒ
A list with all selection figures is included in the chapter
"Configuration"
® "Selection lists".
ƒ
For signal linkage we recommend the function block editor in
GDC (ESP−GDC2).
Description
Linking signals