2 drilling the holes into the mounting plate, Drilling the holes into the mounting plate, Installing of the standard device – Lenze EVF9383 User Manual
Page 54

Installing of the standard device
Basic devices in the power range 250 ... 400 kW
Drilling the holes into the mounting plate
4.3
4.3.2
l
4.3−2
EDSVF9383V EN 7.1−04/2012
4.3.2
Drilling the holes into the mounting plate
Assembly space
Minimum clearance
Left/right of other controllers
30 mm
Left/right of a non−heat−conducting wall
100 mm
Top/bottom
200 mm
Comply with the clearances given to ensure a sufficient cooling of the
controller. When using an air lock, different clearances apply (see Mounting
Instructions for the air lock).
a
a1
a1
a1
a1
a3
a3
a2
a2
a2
a2
d
b
93vec079
Fig. 4.3−2
Bore holes in the mounting plate for fixing the controller
a
a1
a2
a3
b
d
550 mm
450 mm
340 mm
225 mm
1005 mm
9 mm (24x)
1. Mark the bore holes on the mounting plate according to the figure.
2. Drill the holes into the mounting plate.