Configuration, Code table – Lenze EVF9383 User Manual
Page 295
Configuration
Code table
8.5
l
8.5−7
EDSVF9383V EN 4.0−03/2006
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0054 Imot
0.0
{0.1 A}
5000.0 Actual motor current, function
block MCTRL
l
Read only
l
MCTRL−IACT = 100 % = C0022
^
8.2−25
^
8.2−40
C0056 MCTRL−MSET2
−100.00
{0.01 %}
100.00 Read only. The output signal
depends on the operating mode:
l
Current motor current in case
of V/f characteristic control,
function block MCTRL1
l
Torque setpoint in case of
vector control, function block
MCTRL2
^
8.2−25
^
8.2−40
C0057 Max Torque
0
{1 Nm}
5000 Maximum possible torque of the
drive configuration
l
Display only
l
With V/f characteristic control
depending on C0022, C0086,
C0088
l
With vector control depending
on C0022, C0086, C0088,
C0091
C0058 MCTRL−FACT
−600.0
{0.1 Hz}
600.0 Output frequency
l
Display only
l
MCTRL−FACT = 100.0 % =
1000.0 Hz
^
8.2−25
^
8.2−40
C0059 Mot pole no.
1
{1}
50 Pole pair number of the motor
l
Display only
C0061 Heatsink temp
0
{1 °C}
100 Heatsink temperature
l
Read only
l
If the temperature of the
heatsink > 85 °C, the controller
sets TRIP OH
l
Early warning is possible via
OH4, temperature is set in
C0122
See System
Manual
(extension)
C0063 Mot temp
0
{1 °C}
200 Motor temperature
l
Read only
l
Monitoring of the motor
temperature must be
activated.
l
KTY at X8/5, X8/8:
– At 150 °C, TRIP OH3 is set
– Early warning is possible via
OH7, temperature is set in
C0121
l
PTC, thermal contact at T1, T2:
– Release sets TRIP or
warning OH8
^
8.2−25
^
8.2−40
C0064 Utilization
0
{1 %}
150 Device utilisation I×t
l
Read only
l
Device utilisation of the last
180 s operating time
l
C0064 > 100 % triggers
warning OC5
l
C0064 > 110 % limits the ouput
current of the controller to
67 % of the maximum current
in C0022
^
8.2−25
^
8.2−40
C0066 MOTOR LOAD
0
{1 %}
250 Motor load I
2
Чt
^
8.2−25
^
8.2−40