Configuration, Code table – Lenze EVF9383 User Manual
Page 301
Configuration
Code table
8.5
l
8.5−13
EDSVF9383V EN 4.0−03/2006
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0130 DIS: act Ti
Active T
i
times for the speed
setpoint conditioning, function
block NSET
l
Display of the additional
acceleration and deceleration
times for the main setpoint
(C0101, C0103)
l
Activation via binary coding of
C0788/1 ... C0788/4
See System
Manual
(extension)
0
C12/C13
1
Tir1/Tif1
2
Tir2/Tif2
...
...
14
Tir14/Tif14
15
Tir15/Tif15
C0132
s
RFG fly delay
May only be changed by Lenze
service personnel!
C0133
s
HLG fly delay
May only be changed by Lenze
service personnel!
C0134 RFG charac
0
0
Linear
linear
characteristic
Ramp function generator
characteristic, function block NSET
l
Characteristic of the main
setpoint
See System
Manual
(extension)
1
S−shaped
S−shaped
characteristic
C0135 Control word
0
Bit
Assignment
Control word, function block AIF
l
Decimal control word when
networked via automation
interface AIF
l
16−bit information, binary
coded
See System
Manual
(extension)
0
reserved
1
reserved
2
reserved
3
Quick stop
4
reserved
5
reserved
6
reserved
7
reserved
8
Operation inhibited
9
Controller inhibit
10
TRIP SET
11
Trip reset
12
reserved
13
reserved
14
reserved
15
reserved
C0136
Display of the control words in
C0135, AIF−IN and CAN−IN1
See System
Manual
(extension)
1 Ctrl wrd C135
Control word C0135
2 Ctrl wrd CAN
Control word CAN
3 Ctrl wrd AIF
Control word AIF
C0141 FCODE (setval)
0.00
−199.9
{0.01 }
199.99 Main setpoint, freely configurable
code (FCODE)
l
Used as main setpoint in the
basic configurations
C0005 = xxx1
C0142 Start options
May only be changed by Lenze
service personnel!
C0143 limit 2 kHz
0.0
0.0
{0.1 Hz}
20.0 Speed−dependent switching
threshold
l
Threshold for automatic
switching frequency reduction
l
The controller changes
automatically to 2 kHz when
this value falls below the
threshold
^
8.2−25
^
8.2−40