1 general data and operating conditions, General data and operating conditions, Technical data – Lenze EVF9383 User Manual
Page 33

Technical data
General data and operating conditions
3.1
l
3.1−1
EDSVF9383V EN 4.0−11/2007
3.1
General data and operating conditions
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
Protection of persons and equipment
Type of protection
EN 60529
IP20
NEMA 250
Protection against accidental contact according to
type 1
Earth leakage current IEC/EN 61800−5−1 > 3.5 mA
Observe regulations and
safety instructions!
Insulation of control
circuits
IEC/EN 61800−5−1 Safe mains isolation by double (reinforced)
insulation for the terminals X1 and X5.
Basic insulation (single isolating distance) for the
terminals X3, X4, X6, X8, X9, X10 and X11.
Insulation resistance
EN 61800−5−1
< 2000 m site altitude: Overvoltage category III
> 2000 m site altitude: Overvoltage category II
Protective measures
Against short circuit, earth fault (earth−fault
protected during operation, limited earth−fault
protection during mains power−up), overvoltage,
motor stalling, motor overtemperature (input for
PTC or thermal contact)
EMC
Noise emission
EN 61800−3
Cable−guided, up to 50 m motor cable length with
RFI filter: Category C2.
Radiation, with RFI filter and installation in control
cabinet: Category C2
Interference
immunity
IEC/EN 61800−3
Category C3