Code table
8.5
l
8.5−42
EDSVF9383V EN 4.0−03/2006
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0715 Function
0
Function selection, function block
TRANS2
See System
Manual
(extension)
0
Rising trans
Rising edge
1. LOW−HIGH edge at TRANS2−IN
switches TRANS2−OUT = HIGH
2. After the time has elapsed
(C0716), TRANS2−OUT switches
to LOW
1
Falling trans
Falling edge
1. HIGH−LOW edge at TRANS2−IN
switches TRANS2−OUT = HIGH
2. After the time has elapsed
(C0716), TRANS2−OUT switches
to LOW
2
Both trans
Both edges
1. LOW−HIGH or HIGH−LOW edge
at TRANS2−IN switches
TRANS2−OUT = HIGH
2. After the time has elapsed
(C0716), TRANS2−OUT switches
to LOW
C0716 Pulse T
0.001 0.001
{0.001 s}
60.000 Pulse duration, function block
TRANS2
l
After the time has elapsed,
TRANS2−OUT switches to LOW
C0718
s
CFG: IN
1000 FIXED0
^ Selection list 2
Configuration of digital input
signal, function block TRANS2
C0719 DIS: IN
0
1 Function block TRANS2
l
Display of the signal linked in
C0718
C0720 Function
2
Function selection, function block
DIGDEL1
See System
Manual
(extension)
0
On delay
On delay
1. LOW−HIGH edge at DIGDEL1−IN
starts a timing element
2. After the time has elapsed
(C0721), DIGDEL1−OUT
switches to HIGH
1
Off delay
Off delay
1. LOW−HIGH edge at DIGDEL1−IN
starts a timing element and
sets DIGDEL1−OUT = HIGH
2. After the time has elapsed
(C0721), DIGDEL1−OUT
switches to LOW
2
ON/OFF delay
On/off delay
1. LOW−HIGH or HIGH−LOW edge
at DIGDEL1−IN starts a timing
element
2. After the time has elapsed
(C0721),
DIGDEL1−OUT = DIGDEL1−IN
C0721 Delay T
1.000 0.001
{0.001 s}
60.000 Delay time, function block
DIGDEL1
C0723
s
CFG: IN
1000 FIXED0
^ Selection list 2
Configuration of digital input
signal, function block DIGDEL1
C0724 DIS: IN
0
1 Function block DIGDEL1
l
Display of the signal linked in
C0723