l
8.5−56
EDSVF9383V EN 4.0−03/2006
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0879
Resetting control words
l
C0879 = 1 performs one reset
1 Reset C135
0
0
Ready
2 Reset AIF
0
1
Reset
3 Reset CAN
0
C0880
s
^ Selection list 2
Configuration of digital input
signals, function block DCTRL
l
Select parameter set
l
Selection of a parameter set via
binary coding of the digital
input signals
See System
Manual
(extension)
1 CFG: PAR*1
1000 FIXED0 C0880/1 C0880/2 Selected
parameter set
2 CFG: PAR*2
1000 FIXED0
0
0
Parameter set 1
0
1
Parameter set 2
1
0
Parameter set 3
1
1
Parameter set 4
C0881
s
CFG: PAR−LOAD
1000 FIXED0
^ Selection list 2
Configuration of digital input
signal, function block DCTRL
l
LOW−HIGH edge = Load
selected parameter set into
C0880
See System
Manual
(extension)
C0884
Function block DCTRL
l
Display of the signals linked in
C0880 and C0881
See System
Manual
(extension)
1 DIS: PAR*1
2 DIS: PAR*2
3 DIS: PAR−LOAD
C0885
s
CFG: R
51
DIGIN1
^ Selection list 2
Configuration of digital input
signals, function block R/L/Q
l
Truth table:
Inputs Outputs
R
L
R/L
QSP
0
0
0/1
1
1
0
0
0
0
1
1
0
1
1
˘
˘
˘ State is unchanged
See System
Manual
(extension)
C0886
s
CFG: L
52
DIGIN2
^ Selection list 2
C0889
0
1 Function block R/L/Q
l
Display of the signals linked in
C0885 and C0886
1 DIS: R
2 DIS: L
C0890
s
CFG: N−SET
5050 NSET−NOUT
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Speed setpoint
^
8.2−25
^
8.2−40
C0891
s
CFG: M−Add
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Additional torque setpoint or
torque setpoint
^
8.2−40
C0892
s
CFG: Lo−M−LIM
5700 ANEG1−OUT
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Lower torque limit in [%] of
C0057
C0893
s
CFG: HI−M−LIM
19523 FCODE−472/3
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Upper torque limit in [%] of
C0057
C0898
s
CFG: M−LIM
switch
0
0
M−LIM ON
Reduced torque
limit is active
Torque limitation in the field
weakening range, function block
MCTRL
l
If the torque limit is reduced,
the maximum possible torque
in the field weakening range is
lowered with 1/f. This provides
a higher motor stability in the
field weakening range
^
8.2−40
1
M−LIM OFF
Reduced torque
limit is inactive