Lenze EVF9383 User Manual
Page 167
Operating mode
6.8
l
6.8−3
EDSVF9383V EN 7.1−04/2012
The frequency inverter is mainly designed for the applications listed in the
below table.
The table helps you to select the correct operating mode for your application:
ƒ C0006 = 5: V/f characteristic control with constant V
min
boost
ƒ C0006 = 1: Vector control
Power range 110 ... 400 kW
Selection of the operating mode in C0006
Motor cable
shielded
£
100 m
unshielded
£
200 m
Motor cable
shielded
>
100 m
unshielded
>
200 m
Applications with asynchronous motors
recommen
ded
alternativ
ely
recommen
ded
alternativ
ely
Single drives
Drives with constant load
5
1
5
−
Drives with heavy start conditions
1
5
5
−
Travelling drives, conveyor belts
5
1
5
−
Pump drives, fan drives
1)
5
−
5
−
Extruder drives
5
1
5
−
Drives for wire drawing machines
5
1
5
−
Drives for rolling machines
5
1
5
−
Drives for rewinders with dancer
(speed−controlled)
1
5
−
−
Group drives
(the resulting motor cable length is decisive
I
res
)
5
−
5
−
l
res
+ (i
Ǹ
@ (l
1
) l
2
) AAA ) l
i
))
1)
A square voltage characteristic (C0014 = 1) is recommended for this application
)
Note!
Only switch between the operating modes if the controller is
inhibited!
Recommended operating
modes