2 parameter setting, Parameter setting, Ȧȡ ȣ – Lenze EVF9383 User Manual
Page 28: Ȧȣ ȥ, Safety instructions, Thermal motor monitoring parameter setting
Safety instructions
Thermal motor monitoring
Parameter setting
2.2
2.2.2
l
2.2−2
EDSVF9383V EN 7.1−04/2012
2.2.2
Parameter setting
Parameter setting
Code
Meaning
Value range
Lenze setting
C0066
Display of the I
2
xt utilisation of the
motor
0 ... 250 %
−
C0120
Threshold: Triggering of an "OC6" error
0 ... 120 %
0 %
C0127
Threshold: Triggering of an "OC8" error
0 ... 120 %
0 %
C0128
Thermal time constant of the motor
0.1 ... 50.0 min
5.0 min
C0606
Response to "OC8" error
Trip, warning, off
Warning
t
+ * (C0128) @ ln
ȧ
ȡ
Ȣ
1
*
y
) 1
ǒ
IM
Ir
Ǔ
2
@ 100
ȧ
ȣ
Ȥ
I
M
Actual motor current
I
r
Rated motor current
y
C0120 or C0127
ƒ The thermal capacity of the motor is expressed by the thermal motor
time factor (C0128). Please see the rated data of the motor for the
value or ask the manufacturer of the motor.
Diagram for the determination of the release times of a motor with a
thermal motor time factor of 5 min:
I
= 3 × I
mot
r
0
50
100
120
0
100
200
300
400
500
600
700
800
900
1000
t [s]
I t [%]
2
I
= 2 × I
mot
r
I
= 1.5 × I
mot
r
I
= 1 × I
mot
r
9300std105
Fig. 2.2−1
I
2
× t−monitoring: Release times for different motor currents and trigger
thresholds
Imot
Motor current
I
r
Rated motor current
I
2
t
I
2
t load
T
Time
Calculating the release time
Reading the release time off
the diagram