Acceleration, deceleration, braking, stopping
Speed range
6.10
6.10.1
l
6.10−2
EDSVF9383V EN 7.1−04/2012
Features "maximum output frequency" (n
max
):
ƒ For defining fixed setpoints (JOG) C0011 acts as limitation.
ƒ C0011 is an internal scaling value! Therefore, changes must only be
made when the controller is inhibited!
(
Stop!
Set C0011 so that the maximum motor speed is not exceeded.
Otherwise the motor can be destroyed.
Observe the internal speed limits (p = number of motor pole pairs):
ƒ Switching frequency 2/4 kHz: n
max
= 36000/4p min
−1
ƒ Switching frequency 1 kHz: n
max
= 36000/4p min
−1
C0011
Adjusting tips