Configuration – Lenze EVF9383 User Manual
Page 262
Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8.2
8.2.7
l
8.2−46
EDSVF9383V EN 7.1−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0420
s
Encoder const
512
1
{1 inc/rev}
8192 Number of increments for
incremental encoder at X8 or X9
l
Connect incremental encoders
with HTL−level on X9 only
^ 6.7−1
C0421
s
Enc voltage
5.00
5.00
{0.1 V}
8.00 Supply voltage for the incremental
encoder at X8
CAUTION! A wrong entry can
destroy the incremental encoder!
C0497 Nact filter
2.0
0.0
{0.1 ms}
50.0 Filter time constant N
act
for actual
speed value, function block
MCTRL2
l
Internal filtering of the speed
signal for control
l
C0497 = 0 ms: Switched off
^
8.2−40
C0890
s
CFG: N−SET
5050 NSET−NOUT
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Speed setpoint
^
8.2−25
^
8.2−40
C0891
s
CFG: M−Add
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Additional torque setpoint or
torque setpoint
^
8.2−40
C0892
s
CFG: Lo−M−LIM
5700 ANEG1−OUT
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Lower torque limit in [%] of
C0057
C0893
s
CFG: HI−M−LIM
19523 FCODE−472/3
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Upper torque limit in [%] of
C0057
C0898
s
CFG: M−LIM
switch
0
0
M−LIM ON
Reduced torque
limit is active
Torque limitation in the field
weakening range, function block
MCTRL
l
If the torque limit is reduced,
the maximum possible torque
in the field weakening range is
lowered with 1/f. This provides
a higher motor stability in the
field weakening range
^
8.2−40
1
M−LIM OFF
Reduced torque
limit is inactive
C0899
s
CFG: N/M−SWT
1000 FIXED0
^ Selection list 2
Configuration of digital input
signal, function block MCTRL
l
LOW = active speed control
l
HIGH = active torque control
^
8.2−40
C0900
s
CFG: QSP
10250 R/L/Q−QSP
^ Selection list 2
Configuration of digital input
signal, function block MCTRL
l
HIGH = drive performs quick
stop
^
8.2−25
^
8.2−40
C0901
s
CFG: I−SET
1000 FIXED0%
^ Selection list 1
Configuration of analog input
signal, function block MCTRL
l
Setting of integral action
component of the speed
controller
^
8.2−40
C0902
s
CFG: I−LOAD
1000 FIXED0
^ Selection list 2
Configuration of digital input
signal, function block MCTRL
l
HIGH = the integral action
component at MCTRL−I−SET is
accepted by the speed
controller