Lenze EVF9383 User Manual
Page 131
Parameter setting with the XT EMZ9371BC keypad
Commissioning example in vector control mode
6.3
6.3.2
l
6.3−7
EDSVF9383V EN 7.1−04/2012
Note
Switch−on sequence
B
When using a TTL encoder with a number of
increments which cannot be set under C0025:
Set C0025 = 100
Enter the number of increments under C0420
C
If required, compensate a voltage drop in the
incremental encoder cable. Use C0421 to adjust the
supply voltage for the TTL encoder.
D
When using a HTL encoder:
Set C0025 = 101
Enter the number of increments under C0420
17.
Set the maximum speed (C0011)
Lenze setting: 3000 rpm
0 %
[n]
100%
C0011
C0010
See chapter "Commissioning"
®
"Acceleration, deceleration, braking,
stopping"
18.
Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f [ H z ]
f 2
C 0 0 1 1
f 1
0
t i r
t i f
T i r
T i f
t
T
ir
+ t
ir
@
C0011
f2 * f1
(see chapter "Commissioning"
®
"Acceleration, deceleration, braking,
stopping")
19.
Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
+ t
if
@
C0011
f2 * f1
(see chapter "Commissioning"
®
"Acceleration, deceleration, braking,
stopping")
20.
If required, set the quick stop deceleration ramp
(C0105)
Lenze setting: 5.00 s
See chapter "Commissioning"
®
"Acceleration, deceleration, braking,
stopping"
21.
If required, adapt the fixed setpoints JOG.
See code table
A
JOG 1 (C0039/1)
Lenze setting: 1500 rpm
Activation:
X5/E3 = HIGH
B
Further fixed setpoints:
JOG 2 (C0039/2) ... JOG 15 (C0039/15)
22.
Ensure a powerfail−proof saving of the settings in
one of the four parameter sets (C0003)
Use C0003 = 1 to save the settings in parameter
set 1.
Code C0003 is the first code in the
menu "Setup V/f".
After switching on the DC 24 V supply
or mains connection, parameter set 1 is
automatically activated.
(see chapter "Parameter setting")
23.
Switch on the mains if the external DC 24 V supply
voltage is switched on only.
24.
Enable controller
misc009
59
28
X5
}
Terminal X5/28 = HIGH
(see chapter "Commissioning"
®"controller inhibit")
25.
Enter the setpoint
Analog setpoint
selection:
−10 ... +10 V via
potentiometer at X6/1
and X6/2
Fixed speed:
Activate JOG 1 with
X5/E3 = HIGH
JOG 1 is parameterised in C0039/1