Configuration, Code table – Lenze EVF9383 User Manual
Page 310
Configuration
Code table
8.5
l
8.5−22
EDSVF9383V EN 4.0−03/2006
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0325 Vp2 adapt
1.0
0.1
{0.1 }
500.0 Function block PTCTRL1
l
Adaptation of gain V
p2
See System
Manual
(extension)
C0326 Vp3 adapt
1.0
0.1
{0.1 }
500.0 Function block PTCTRL1
l
Adaptation of gain V
p3
C0327 Set2 adapt
100.0
0
0.00
{0.01 %}
100.00 Function block PTCTRL1
l
Adaptation of setpoint speed
threshold n
set2
l
Condition: C0327 > C0328
C0328 Set1 adapt
0.00
0.00
{0.01 %}
100.00 Function block PTCTRL1
l
Adaptation of setpoint speed
threshold n
set1
l
Condition: C0328 < C0327
C0329 Adapt on/off
0
0
No adaptation of the process controller Function block PTCTRL1
l
Adaptation On/Off
1
External adaptation via input
2
Adaptation via setpoint
3
Adaptation via control difference
C0332 PCTRL Tir
0
0
{1 s}
10000 Acceleration time T
ir
, function
block PCTRL1
l
The acceleration time refers to
a setpoint change of 0 ... 100 %
See System
Manual
(extension)
C0333 PCTRL1 Tif
0
0
{1 s}
10000 Deceleration time T
if
, function
block PCTRL1
l
The deceleration time refers to
a setpoint change of 100 % ... 0
C0336 DIS: act Up
0.0
{0.1 }
500.0 Current gain V
p
, function block
PCTRL1
l
Read only
See System
Manual
(extension)
C0337 Bi/unipolar
0
Sphere of action, function block
PCTRL1
0
Bipolar
l
Output value is limited to
−100 ... 100 %
1
Unipolar
l
Output value is limited to
0 ... 100 %
C0338 ARIT1 funct
1
0
OUT = IN1
Selection of function, function
block ARIT1
See System
Manual
(extension)
1
OUT = IN1 + IN2
2
OUT = IN1 − IN2
3
OUT = IN1 * IN2
4
OUT = IN1 / IN2
5
OUT = IN1 / (100 − IN2)
C0339
s
^ Selection list 1
Configuration of analog input
signals, function block ARIT1
1 CFG: IN
1000 FIXED0%
ARIT1−IN1
2 CFG: IN
1000 FIXED0%
ARIT1−IN2
C0340
−199.99
{0.01 %}
199.99 Function block ARIT1
l
Display of the signals linked in
C0339
1 DIS: IN
ARIT1−IN1
2 DIS: IN
ARIT1−IN2
C0350 CAN address
1
1
{1}
63 System bus node address
l
Change is effective after ˜Reset
node˜ command
C0351 CAN baudrate
0
0
500 kbit/s
System bus baud rate
l
Change is effective after ˜Reset
node˜ command
1
250 kbit/s
2
125 kbit/s
3
50 kbit/s
4