Adjusting the motor
Motor temperature monitoring with KTY
6.6
6.6.4
l
6.6−11
EDSVF9383V EN 7.1−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0594 MONIT SD6
3
0
TRIP
Activation of the motor
temperature monitoring with KTY
at X8
l
Use C0594 = 0 or 2 to activate
monitoring
l
In case of a short circuit or
interruption at X8/5 and X8/8
the fault message SD6 is
activated
l
Configuration of the response
when exceeding the motor
temperature
– Fixed operating temperature
in C0583
– Variable operating
temperature in C0584
^
6.6−10
See System
Manual
(extension)
2
Warning
3
Off
C1190 Motor PTC
selection
0
Temperature characteristic for PTC
thermistors
l
Selection of the characteristic
for PTC thermistors at X7 or X8
for detecting the motor
temperature
^
6.6−10
0
Standard
Characteristic for PTC thermistors
in Lenze motors
1
Characteristic
Characteristic for
application−specific PTC
thermistors
C1191 Temperature
characteristic
0
{1 °C}
255 Temperature range for PTC
thermistors
l
Define temperature points on
the characteristic for PTC
thermistors
1 Temperature 1
100
Temperature point 1
2 Temperature 2
150
Temperature point 2
C1192 Resistance
characteristic
0
{1
W}
3000 Resistance characteristic for PTC
thermistors
l
Define resistance points on the
characteristic for PTC
thermistors
1 Resistance 1
1670
Resistance point 1
2 Resistance 2
2225
Resistance point 2