Switching frequency of the inverter
6.9
l
6.9−2
EDSVF9383V EN 7.1−04/2012
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0018 fchop
6
Switching frequency of the
inverter
l
General rule: The lower the
switching frequency the
– lower the power loss
– higher the noise generation
– better the concentricity
factor
l
Observe derating indications
for high switching frequencies
l
The max. output frequency
(f
max
) is:
– fchop = 4 kHz
Þ
f
max
= 300 Hz
– fchop = 2 kHz
Þ
f
max
= 150 Hz
– fchop = 1 kHz
Þ
f
max
= 150 Hz
^
6.9−1
1
1 kHz sin
loss−optimised
2
2 kHz sin
concentricity−opti
mised
3
4 kHz f_top
power−optimised
4
4 kHz sin
noise−optimised
6
4/2 kHz sin
noise/concentricit
y−optimised with
automatic
change−over to
low switching
frequency
C0144
s
OH switch
1
0
Switch off
Switch−over is not
active
Temperature−dependent
switching frequency reduction
l
If the heatsink temperature set
in C0122 is reached (warning
OH4), the controller switches
to 2 kHz
1
Switch on
Switch−over is
active
C0144 = 0 (no temperature−dependent switching frequency reduction)
If the maximum permissible heatsink temperature (
J
max
) is exceeded when
operating with automatic switching frequency reduction, the inverter is
inhibited, TRIP "OH" (overtemperature) is set and the motor coasts without
torque.
C0144 = 1 (temperature−dependent switching frequency reduction is
active):
ƒ If the heatsink temperature set in C0122 (overtemperature OH4) is
reached when operating with automatic switching frequency
reduction, the controller automatically reduces the switching
frequency to 2 kHz, thus keeping the operation running.
ƒ After the heatsink has cooled down, the controller automatically
switches to the set switching frequency again.
Function of automatic
switching frequency
reduction