Configuration, Code table – Lenze EVF9383 User Manual
Page 305

Configuration
Code table
8.5
l
8.5−17
EDSVF9383V EN 4.0−03/2006
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0173
s
UG limit
1
Check during commissioning and
adapt, if necessary!
All controllers in the system must
have the same threshold!
l
Adaptation of UG thresholds
l
Only display in case of the
variants for 400 V mains
(EVF93xx−EV, EVF93xx−EVV030,
EVF93xx−EVV060,
EVF93xx−EVV110):
– C0173 = 1
– OU = 700 ... 685 V
^ 12−1
See System
Manual
(extension)
Mains
LU
OU
0
< 400 V
285 V
770 ... 755 V
Device with or without brake
transistor
1
400 V
285 V
770 ... 755 V
2
460 V
328 V
770 ... 755 V
3
480 V
342 V
770 ... 755 V
Device without brake transistor
4
480 V
342 V
800 ... 785 V
Device with brake transistor
5
500 V
342 V
900 ... 885 V
C0174 BR Limit
3
Display of the brake transistor
thresholds
Check during commissioning and
adapt, if necessary!
All controllers connected to the
bus must have the same
threshold!
^ 12−1
See System
Manual
(extension)
Mains
U
BR
OU
0
400 V
685 V
700 V
Only display in case of the variants
for 400 V mains (EVF93xx−EV,
EVF93xx−EVV030,
EVF93xx−EVV060,
EVF93xx−EVV110)
1
400 V / 460 V
755 V
770 V
Only in case of the variants for
400 V/500 V mains
(EVF93xx−EVV210,
EVF93xx−EVV240,
EVF93xx−EVV270,
EVF93xx−EVV300)
2
480 V
785 V
800 V
3
500 V
885 V
900 V
C0178 Op timer
{s}
Display only
Total time of the controller enable
(X5/28 = HIGH)
C0179 mainstimer
{s}
Display only
Total time of mains "ON"
C0182 Ti S−shaped
20.00 0.01
{0.01 s}
50.00 Integration time of S−shaped ramp
function generator, function block
NSET
l
C0182 = 0.00: ramp function
generator operates linearly
l
C0182 > 0.00: ramp function
generator operates in an
S−shape (without jerk)
See System
Manual
(extension)