Lenze EVF9383 User Manual
Page 157
Adjusting the motor
Automatic collection of motor data
6.6
6.6.6
l
6.6−17
EDSVF9383V EN 7.1−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0148
s
ident run
0
0
WRK
stop
Ready
Motor data identification
1. Inhibit controller, wait until
drive has stopped
2. Enter the correct values of the
motor nameplate into C0087,
C0088, C0089, C0090, C0091
3. Set C0148 = 1, confirm with
v
4. Enable controller
The identification
– starts,
c goes off. The
motor "whistles" but does
not rotate!
– lasts approx. 1 ... 2 min
– is completed when
c is lit
again
5. Inhibit controller:
^
6.6−15
1
WRK run Start identification
C0149
s
Auto ident
0
0
Id
inactive
Automatic identification is
inactive
Automatic motor data
identification
1. Inhibit controller, wait until
drive has stopped
2. Enter the correct values of the
motor nameplate into C0087,
C0088, C0089, C0090, C0091
3. Set C0149 = 1, confirm with
v
4. Enable controller
The identification
– starts,
c goes off. The
motor "whistles" but does
not rotate!
– lasts approx. 1 ... 2 min
– is completed when
c is lit
again
5. Inhibit controller:
^
6.6−15
1
Id active Automatic identification is
active
l
The identification starts
automatically after
controller enable
l
After a faulty
identification, the process
is restarted after TRIP
RESET or mains switching
and subsequent
controller enable