Configuration – Lenze EVF9383 User Manual
Page 259
Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8.2
8.2.7
l
8.2−43
EDSVF9383V EN 7.1−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0056 MCTRL−MSET2
−100.00
{0.01 %}
100.00 Read only. The output signal
depends on the operating mode:
l
Current motor current in case
of V/f characteristic control,
function block MCTRL1
l
Torque setpoint in case of
vector control, function block
MCTRL2
^
8.2−25
^
8.2−40
C0058 MCTRL−FACT
−600.0
{0.1 Hz}
600.0 Output frequency
l
Display only
l
MCTRL−FACT = 100.0 % =
1000.0 Hz
^
8.2−25
^
8.2−40
C0063 Mot temp
0
{1 °C}
200 Motor temperature
l
Read only
l
Monitoring of the motor
temperature must be
activated.
l
KTY at X8/5, X8/8:
– At 150 °C, TRIP OH3 is set
– Early warning is possible via
OH7, temperature is set in
C0121
l
PTC, thermal contact at T1, T2:
– Release sets TRIP or
warning OH8
^
8.2−25
^
8.2−40
C0064 Utilization
0
{1 %}
150 Device utilisation I×t
l
Read only
l
Device utilisation of the last
180 s operating time
l
C0064 > 100 % triggers
warning OC5
l
C0064 > 110 % limits the ouput
current of the controller to
67 % of the maximum current
in C0022
^
8.2−25
^
8.2−40
C0070 Vp speed CTRL
10.0
0.0
{0.1 }
255.9 Gain of speed controller
^
8.2−25
^
8.2−40
C0071 Tn speed CTRL
50
1
{1 ms}
6000 Integral−action time of speed
controller
C0071 = 6000 ms: No
integral−action time
C0075 Vp curr CTRL
0.04
0.00
{0.01 }
0.99 Gain of current controller
l
Vector control: Gain of current
controller
l
V/f characteristic control:
Maximum current controller
^
8.2−25
^
8.2−40
C0076 Tn curr CTRL
10.0
0.1
{0.1 ms}
2000.0 Integral−action time of current
controller
l
Vector control: integral−action
time of current controller
l
V/f characteristic control:
maximum current controller
l
C0076 = 2000 ms: current
controller is switched off
^
8.2−25
^
8.2−40
C0082
s
Mot Rr
à
0.0000
{0.0001
W}
65.5350 Motor rotor resistance
à
Value is determined by motor
parameter identification from
C0087, C0088, C0089, C0090
and C0091
l
Selection of a motor in C0086
sets the corresponding rotor
resistance value
^ 6.6−1
^
6.6−15