CH9: Diagnostics

MAN0575-04-EN

PAGE 73 of 97

© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.

Profibus Modules User Manual

EO 09-0009


















Figure 56: Save a Message


10.3

Message Monitor for Testing of DPV1 (Master)

The following steps show how to configure the Message Monitor for reading and writing via DPV1
from the Master:
Enter the following in the Message Monitor in order to read data via DPV1 from a Slave:


Message for Read via DPV1
Message header

Rx = 3 (always)

Tx = 255

Ln = (calculated)

Nr = 0 .. 255

A = 0

F = 0

B = 17

E = 0

Telegram header

Meaning for DPV1

Value range

Device Adr

Station address of the Slave 0 .. 126

Data Area

Unused

0

Data Address

Slot

0 .. 254

Data Index

Index

0 .. 255

Data Count

Data Count

1 .. 240

Data Type

Data Type

10

Function Read

1

Table 16: Message Monitor – Example DPV 1 Read


The following must be entered in the Message Monitor in order to write data via DPV1 to a Slave:

Message for Write via DPV1

Message header

Rx = 3 (always)

Tx = 255

Ln = (calculated)

Nr = 0 .. 255

A = 0

F = 0