Horner APG SmartStack I/O HE800PBS600/HEPBS600 User Manual
Page 53
Online Functions
MAN0575-04-EN
PAGE 53 of 97
© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.
Profibus Modules User Manual
EO 09-0009
In the window Actual Network Constellation the text in the columns Found Slave and Real
Configuration Data can be displayed in the following colours:
Colour
Found Slave
Real Configuration Data
0 Orange For this device no suitable GSD file was
found
No suitable modul was found in
the GSD file
1 Black For this device exactly one suitable GSD
file was found
Exactly one modul was found in
the GSD file
≥2 Blue
For this device more than one suitable
GSD file was found
More than one modul was
found in the GSD file
Table 10: Network scan - Description of the displayed window
If a device is coloured, red in the Actual Network Constellation an error has occurred. For
example, a Slave with the Station Address 126 was detected. In this case, the Ident number cannot
be read out.
Upon exiting the window Actual Network Constellation, the System Configurator provides the option
as too whether the constellation should be taken into the configuration or not.
Figure 37: Online > Automatic Network Scan > Accept Configuration
Example:
This example shows a scanned Network Constellation with more than one suitable module for the
GSD file. The modules (Real Cfg. Data) are coloured blue, which means, that the assignment can be
changed by clicking the Assign Module button:
Figure 38: Online > Automatic Network Scan - Example for Assignment
8.6 Assign
Slave
The identnumber is read from the Slave device during the network scan. If more than one GSD file is
available with this identnumber in the window Assign Slave, a list is displayed and the correct Slave
device may be selected.