CH9: Diagnostics

MAN0575-04-EN

PAGE 67 of 97

© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.

Profibus Modules User Manual

EO 09-0009

NEXC

NON-EXCHANGE-ERROR at least one Slave has not reached the data
exchange state and no process data exchange is done.

ACLR

AUTO-CLEAR-ERROR device stopped the communication to all Slaves and
reached the auto-clear end state.

CTRL CONTROL-ERROR

parameterisation error.

Table 14: Meaning of collecting status bits in the Global State Field

Further displays are:
Collective online error location and corresponding error gives the station address and the error
text.
Statistic bus information displays the number of the detected bus short circuits and the number of
rejected telegrams.

Device specific status bits:
Parameterised Devices, Activated Devices and Devices with Diagnostic are shown the buttons
are clicked. The activated addresses are coloured numbers. This application updates online the
status in the global state field. The diagnostic may be seen by double-clicking on a highlighted station
address of a device.


9.7

Extended Device Diagnostic

The Extended Device Diagnostic helps to find bus and configuration errors when the HSyCon menu
functions are of no further help. First, the desired device must be chosen with a left mouse click on
the symbol of the device. Then, select the Online > Extended Device Diagnostic menu.
This menu opens a list of diagnostic structures. These contain online counters, states and parameter
information:










Figure 51: Extended Device Diagnostic as and example for the PROFIBUS-DP.