CH9: Diagnostics
MAN0575-04-EN
PAGE 68 of 97
© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.
Profibus Modules User Manual
EO 09-0009
9.8 I/O
Monitor
This is an easy way of viewing and changing the first 32 Bytes of the process data image. To open
the I/O Monitor select the menu Online > I/O Monitor.
Figure 52: Online > I/O Monitor
DEC/HEX sets the representation of the input data. The output data is always in the decimal form.
Enter the output value and then press Update. Only the first 32 input and output Bytes of the process
depiction are shown, even when these Bytes have not been set by the configuration. The display is
always in a Byte manner.
9.9 I/O
Watch
The I/O Watch monitor can be used in place of the I/O Monitor and offers more functionality including:
Various data formats: Hex, Unsigned Decimal, Signed Decimal, Bit.
The I/O Watch monitor works symbol oriented.
It is not necessary to know the offset addresses.
The following firmware supports the I/O Watch monitor function:
Fieldbus From
Version
PROFIBUS-DP Master 1.040 (Combimaster) resp. 1.140 (DP-
Master)
InterBus Master
2.040
CANopen Master
1.040
DeviceNet Master
1.058
AS-Interface Master
1.010
Table 15: Firmware for I/O Watch function