1 GENERAL

SPECIFICATIONS

General Specifications

Storage
Temperature

-25

° to 70° C

Operating
and Storage
Humidity

5 to 95% Non-condensing

Operating
Temperature

0

° to 55° C

Pollution
degree

2 or lower

Atmosphere

Free from corrosive

gases and

excessive dust

Cooling
method

Self-cooling

Vibration

Occasional Vibration

Frequency Acceleration

Amplitude

Sweep

Count

10

≤ f < 57 Hz

- 0.075

mm

57

≤ f ≤ 150 Hz

9.8 m/s

2

{1G} -

10 times in each

direction for

X,Y,Z

Continuous Vibration

Frequency Acceleration

Amplitude

Sweep

Count

10

≤ f < 57 Hz

- 0.035

mm

57

≤ f ≤ 150

Hz

4.9 m/s

2

{0.5G} -

10 times in each

direction for

X,Y,Z

Shocks

Maximum shock
acceleration

147 m/s

2

{15G}

Duration Time

11 ms.

Pulse Wave

Half sine wave pulse (3 times in each of X, Y, Z directions)

Noise Immunity

Square wave
impulse noise

AC: ± 1,500VDC

DC: ± 900VDC

Electrostatic
Discharge

Voltage: 4kV (contact discharge)

Radiated
electromagnetic
field

27 – 500MHz, 10V/m

Severity

level

All power

modules

Digital I/Os

(Ue

≥24V)

Digital I/Os

(Ue < 24 V)

Analog I/Os

Communication

I/Os

Fast Transient
Burst Noise

Voltage

2 kV

1 kV

0.25 kV



2 DIMENSIONS


a. DQM602














SmartStix

TM

HE559DQM602



Remote I/O for the OCS/RCS Family


16 Relay Outputs (250VAC, 30VDC, 2.0A)



b. Terminal Strips















3 NETWORK

CABLE

For detailed wiring information, refer to the Control Station Hardware Manual. A
handy checklist is provided that covers panel box layout requirements and minimum
clearances. See Section 10 for our web address.

Pin

Description

RED 1 V+

WHT 2 CAN_H

NC 3 No

Connection

BLU 4 CAN_L

BLK 5 V-

4 ID

SWITCHES

(SETTING CSCAN NETWORK IDs)

CsCAN Network IDs are set using the hexadecimal number system from 01 to FD. The
decimal equivalent is 1-253. Refer to Section 8, which shows the decimal equivalent of
hexadecimal numbers. Set a unique Network ID by inserting a small Phillips screwdriver
into the two identical switches. Note: The CsCAN Baud Rate for SmartStix I/O is fixed at
125KBaud.














5 LEDs

a. Diagnostic LED Indicators

Diagnostic LED

State

Meaning

Solid Red

RAM or ROM test failed

Blinking Red

I/O test failed

Blinking Green

Module is in power-up state

MS: (indicates fault status of
Module )

Solid Green

Module is running normally

Solid Red

Network Ack or Dup ID test failed

Blinking Red

Network ID test failed

Blinking Green

Module is in Life Expectancy default

state

NS: (indicates fault status of
Network)

Solid Green

Network is running normally


b. Status LED Indicators

The Power Status LED illuminates Red when power is applied to the module. There are
I/O Status LED indicators for each of the Digital I/O points, which illuminate Red when an
I/O point is ON.

1.87

0.31

HE559-With Removable

Strip

6.95 [176.5mm]

6.61 [167.9mm]

1.62 [41.1mm]

0.18 [4.6mm]

1.97 [49.9mm]

Close-up of Switches

006DIM001

Use this switch to set
the Low Digit – has
an x1 multiplier.

Use this switch to set the
High Digit –has an x16
multiplier.

I/O Status LEDs

Power and Diagnostic

LEDs

INPUT
S

LO (x1)

HI (x16)

MS

NS

PWR

SmartStix I/O

2

1

4

5

6

7

8

11

3

9

12 13 14 15 16

10

INPUTS

LO (x1)

HI (x16)

MS

NS

PWR

SmartStix I/O

2

1

4

5

6

7

8

11

3

9

12 13 14 15 16

10

Recommended Cable

Thick:
(Max Distance =
500m)

Belden 3082A

Thin:
(Max Distance =
100m)

Belden 3084A