Chapter 7: dp slave – Horner APG SmartStack I/O HE800PBS600/HEPBS600 User Manual
Page 42
DP Slave
MAN0575-04-EN
PAGE 42 of 97
© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.
Profibus Modules User Manual
EO 09-0009
CHAPTER 7: DP SLAVE
7.1 Slave
Settings
The DP Slave Settings contain parameters that define the behaviour of the device at the user
interface, which do not belong to the DP configuration. This menu point is applicable only to Horner
devices. These settings are transferred with the download of the DP configuration to the device. In
order to open the DP Slave settings menu, first choose the Slave by clicking on it and then open the
window in the Settings > DP Slave Settings menu.
Figure 19: DP Slave Settings
Handshake of the process data
These various functions select the Handshake of the process data of the Slave. The selection of
the function is important for the correct data exchange between the application and the device.
Select ‘Buffered Host Controlled’ for all Horner Slave modules.
Configuration mode
If the Slave device is to use the parameters of the configuration that is downloaded from SyCon
then the Configuration by SYstem CONfigurator mode must be selected for the Configuration
mode. If the DP configuration is written online from an application into the Dual-port memory,
then the Configuration by Application mode must be selected.