CH9: Diagnostics

MAN0575-04-EN

PAGE 60 of 97

© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.

Profibus Modules User Manual

EO 09-0009






















.

Figure 47: Online > Device Diagnostic

Station Status 1, 2 and 3 is described on the next page.
The Assigned Master Address is the address of the master, which has parameterised and
configured this Slave. If the value 255 is displayed, it means that the Slave reports that either
It is not parameterised or configured yet

That the received parameter information and configuration information have been rejected because of
an error.

The Real Ident Number is the ident number from the DP Slave connected. The GSD Ident Number
is the ident number from the GSD file read by the HSystem Configurator. Both ident numbers must
be the same. If they are different, the reason may be either:
The wrong GSD file has been read.

The DP Slave connected is the wrong one.


When the Real Ident Number is 0000, then the master has no connection via the PROFIBUS to the
DP Slave.