1 Specifications
THM100
THM200
THM100 THM200
Number of
Channels
4 8
Conversion
Time (PLC
Update Rate)
Determined by
Communications
w/OCS
Input
Ranges
J, K, R, S,B,E,T,N,
+/-50mV, +/-
100mV, +/-500mV,
+/-1V
Terminal
Type
Screw Type,
Removable
Resolution
0.1C or 0.001mV
Storage
Temp.
-40
° to 85°
Celsius
Operating
Temp.
-10
° to 60°
Celsius
Input
Impedance
>10MOhm
Relative
Humidity
5 to 95% Non-
condensing
Accuracy +/-0.1%
F.S.
Dimensions
WxHxD
17.5mm x
100mm x
120mm
0.69” x 3.94” x
4.72”
External
Power
Supply
Voltage
10-30Vdc
Weight
150g (6 oz.)
Required
Power
(Steady
State)
30mA @ 24Vdc,
typical
Communicati-
ons
Modbus/RTU
(binary)
RS-485 half duplex
Required
Power
(Inrush)
Negligible
Factory
Default
Communicati-
ons
Parameters
38400 baud, N, 8,
1, no h/s
Default Modbus ID
1
Isolation
2000Vac for 60
seconds
(Input/Power &
Input/Comms)
Supported
Modbus
Commands
1,2,3,4,5,6,8,15,16
CE & UL
Compliance
See Compliance Table at
2 Wiring
–
I/O
SmartMod
Thermocouple Input Module
HE359THM100 / HE359THM200
0.1C or 0.001mV Resolution
Dimensions in inches are 0.69”W x 3.95”H x 4.72”D
Note: Number of I/O terminal connections vary from model to model
I/O
RS-485
DC IN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
V+
GNA
V+
GNA
V+
GNA
V+
GNA
V+
GNA
V+
GNA
V+
GNA
V+
GNA
IN
0
IN
1
IN
2
IN
3
IN
4
IN
5
IN
6
IN
7
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
Pin #
ADC107
ADC207
Pin #
ADC107
ADC207
1
INPUT 0+
INPUT 0+
9
INPUT 4+
2
ANALOG
COMMON
ANALOG
COMMON
10
ANALOG
COMMON
3
INPUT 1+
INPUT 1+
11
INPUT 5+
4
ANALOG
COMMON
ANALOG
COMMON
12
ANALOG
COMMON
5
INPUT 2+
INPUT 2+
13
INPUT 6+
6
ANALOG
COMMON
ANALOG
COMMON
14
ANALOG
COMMON
7
INPUT 3+
INPUT 3+
15
INPUT 7+
8
16
Only Terminals 1
through 8 are
present on the
ADC107 model
ANALOG
COMMON
ANALOG
COMMON
ANALOG
COMMON
D-
D+
GND
INIT
A
B
C
D
V-
V+
I
J
10-30Vdc
Notes:
Both ends of the RS-485 network should be terminated with a 100ohm, 1/4W, 1% resistor. Many OCS
controllers feature dip switches or jumpers which enable appropriate termination if the OCS is located on
a network end.
Wiring RS-485
Wiring DC IN