Profibus Modules User Manual

EO 09-0009

4.5

PROFIBUS-DP Auto Configuration



The Auto Configuration can be used to configure a Slave. The parameter data cannot be retrieved
from a PROFIBUS-DP Slave. Thus, if the Slave requires parameter data, it must be provided by the
user. The following is the procedure for Auto Configuration:

Action

Menu in the System Configurator

1Create a new project

File > New > PROFIBUS

2Copy GSD file of the DP Slave, if the Slave is not in the

selection list

File > Copy GSD

3Choose Horner DP Master and provide bus address

Insert > Master

4Choose DP Slave and provide bus address

Insert > Slave

5Set the bus parameter

Mark the Master (left Mouse click), then
Settings > Bus Parameters

6Set device assignment if no automatic assignment has

occurred

Mark the Master (left Mouse click), then
Settings > Device Assignment

7Save project

File > Save

8Download

Mark the Master (left Mouse click), then
Online > Download

9Live List

Mark the Master (left Mouse click), then
Online > Live List

1
0

Start Debugger

Mark the Master (left Mouse click), then
Online > Start Debug Mode

1
1

Device diagnostic

Mark the Slave (left Mouse click), then
Online > Device Diagnostic

1
2

Compare Configuration

Compare Configuration

1
3

Automatic configuration

Automatic Configuration

1
4

Stop Debugger

Online > Stop Debug Mode

1
5

Save project

File > Save

1
6

Download

Mark the Master (left Mouse click), then
Online > Download

1
7

Start Debugger

Mark the Master (left Mouse click), then
Online > Start Debug Mode

1
8

Device diagnostic

Mark the Slave (left Mouse click), then
Online > Device Diagnostic

1
9

Stop Debugger

Online > Stop Debug Mode

2
0

Transfer user data:
Write output, read input

Mark the Master (left Mouse click), then
Online > I/O Monitor

Figure 4.5. Auto Configuration (PROFIBUS-DP)


4.6 Replace

Master

If a Master already exists in the configuration and should be replaced for another Master, first set the
focus on the Master (left mouse click on the Master) and then choose the menu Edit > Replace or